IC693ACC335 数字式伺服轴端子板

IC693CPU331_副本1.jpg

 

 

【功能描述】

 

IC693ACC335是GE发那科公司的数字式伺服轴端子板。该端子板用于将DSM连接器A和B连接到GE发那科数字伺服放大器上的相应连接器。此外,伺服板提供螺丝端子连接不同的I/O设备。GE Fanuc IC693ACC335端子板有2个连接器,每个连接器36脚。其中一个连接器被标记为DSM连接器,用户可以用电缆将其连接到DSM设备。另一个连接器标记为“SERVO”连接器,用户可以将其连接到GE发那科数字伺服放大器上。用户将需要伺服命令电缆,如IC800CBL001或002命令电缆,以实现此连接。


如果数字伺服轴不需要将IC693ACC335端子板连接到螺钉端子板的任何设备,则用户不需要端子板电缆或端子板。在这种情况下,用户可以直接将数字伺服命令电缆从数字伺服放大器连接到DSM面板。这可以通过A或B连接器完成。用户必须确保正确配置“OT Limit Sw”设置。此设置必须处于“DISABLE”位置,否则DSM无法运行。如果IC693ACC335端子板不用于断开用户I/O点,如家庭限制输入,则用户必须在DSM面板的前部插入电缆的另一端。电缆必须插入连接器A,这意味着伺服轴1或连接器B,这是伺服轴2设置。

IC693ACC335 数字式伺服轴端子板

IC693CPU331_副本1.jpg

The IC693ACC335 is a digital servo axis terminal board by GE Fanuc. This terminal board is used to connect DSM connectors A and B to the corresponding connectors on a GE Fanuc digital servo amplifier. Additionally, the servo board provides screw terminal connections for different I/O devices. The GE Fanuc IC693ACC335 terminal board has 2 connectors, and each connector has 36 pins. One of the connectors is labeled as a DSM connector and the users can connect it to the DSM device with a cable. The other connector is labeled as the "SERVO" connector, and the users can connect it to the GE Fanuc digital servo amplifier. The users will need servo command cables like the IC800CBL001 or 002 command cables for this connection to be possible.

In the event that a digital servo axis does not need any devices that connect the IC693ACC335 terminal board to the screw terminal board, then users do not need a terminal board cable or a terminal board. In that case, it is possible for the users to directly connect the digital servo command cable from a digital servo amplifier to the DSM faceplate. This can be done through the A or B connectors. It is essential for the users to make sure that they correctly configure the "OT Limit Sw" setting. This setting must be in the "DISABLE" position, otherwise the DSM cannot run. If the IC693ACC335 terminal board is not being used for breaking out the user I/O points like home limit inputs, the users must insert the other end of the cable differently on the front part of the DSM faceplate. The cable must be inserted into Connector A, which is meant for Servo Axis 1 or into Connector B, which is set for Servo Axis 2.


 

姗姗名片合并2(1).jpg


 

 

【联系我们】

 

厦门雄霸电子商务有限公司

厦门市思明区吕岭路1733号创想中心2009-2010单元

联系人:珊妮

电话:18059884797